Outsource Water Treatment, Not Responsibility

1 hour ago
6 min read

One of the growing concerns we've noticed at MySafety while visiting industrial ammonia refrigeration facilities is the increasing reliance on third-party companies to manage evaporative condenser water treatment programs. While there's absolutely nothing wrong with utilizing a company that specializes in water treatment, problems begin to arise when refrigeration operators no longer give their condenser water conditions any attention because "someone else is responsible for it."


We've personally witnessed situations where this mentality has contributed to equipment deterioration and operational issues that potentially could have been prevented through routine operator involvement. Water treatment specialists understand water chemistry, but that doesn't necessarily mean they understand the design, operation, and hazards associated with an industrial ammonia refrigeration system. This is where the knowledge of both parties needs to come together.


Your condenser is more than a cooling tower

Although evaporative condensers and cooling towers share many similarities in how they reject heat, there is one significant difference that needs to be recognized. An evaporative condenser in an industrial ammonia refrigeration system contains pressurized ammonia within its condenser coils. The same surfaces being continuously exposed to chemically treated water are part of the pressure-containing boundary of your ammonia refrigeration system.


Improper water treatment is not simply a concern about water quality or equipment efficiency. It can directly impact the mechanical integrity of your ammonia refrigeration system. Deterioration of a condenser sump may result in a water leak. Deterioration of a condenser coil could result in an ammonia release. That is a significant difference in consequences.


What is the purpose of condenser water treatment?

When water evaporates from a condenser, the dissolved minerals within the water remain behind. As makeup water is introduced to maintain the sump level, additional minerals are introduced into the recirculating water. Without proper water management, these minerals continue to concentrate, creating conditions that can contribute to scale formation, corrosion, and biological growth.


A properly developed water treatment program should address four primary areas:

  • Scale control: Preventing mineral deposits from accumulating on heat transfer surfaces.

  • Corrosion control: Protecting metallic surfaces from chemical deterioration.

  • Biological control: Controlling bacteria, algae, biofilm, and microorganisms, including Legionella.

  • Cycles of concentration: Managing the accumulation of dissolved minerals through controlled blowdown and makeup water.


However, simply having chemical drums, metering pumps, and an automated water treatment controller installed does not guarantee that any of these conditions are being properly controlled.


Understanding the chemicals being introduced into your condenser

How many ammonia refrigeration operators know what chemicals are currently being introduced into their condenser sumps? Furthermore, do they understand what each of those chemicals is intended to accomplish?


Some common chemical applications include:

Chemical application

Intended purpose

Potential concerns

Corrosion inhibitors

Protect metallic surfaces

Inadequate protection or material incompatibility

Scale inhibitors

Minimize mineral deposits

Reduced heat transfer if treatment is ineffective

Oxidizing biocides

Control biological growth

Accelerated corrosion when improperly applied

Non-oxidizing biocides

Control microorganisms

Ineffective biological control or compatibility concerns

Acid-based treatments

Reduce pH and manage alkalinity

Deterioration of metallic surfaces if overdosed

Dispersants

Help keep deposits suspended

Accumulation of deposits if treatment is ineffective

Passivation chemicals

Establish a protective layer on metallic surfaces

Premature deterioration of galvanized surfaces


More chemicals do not necessarily mean better water treatment. Overfeeding chemicals can be just as detrimental to your equipment as underfeeding them. Chemical selection, concentration, application frequency, and injection location.


Understanding your condenser's materials of construction

Not all evaporative condensers are manufactured using the same materials, and not all materials have the same tolerance for water chemistry. For example, a facility may have stainless steel condenser sumps but galvanized steel condenser coils. It's even common for facilities to have older condensers with galvanized steel coils and newer condensers with stainless steel coils, all sharing the same treated sump water. A water treatment program developed around the limitations of stainless steel may not be suitable for the galvanized steel surfaces. Below is an example of water chemistry guidelines published by EVAPCO for evaporative cooling equipment.


Water parameter

G-235 galvanized steel

304 stainless steel

316 stainless steel

pH

7.0–8.8

6.0–9.5

6.0–9.5

Conductivity (µS/cm)

Below 2,400

Below 4,000

Below 5,000

Alkalinity as CaCO₃ (ppm)

75–400

Below 600

Below 600

Calcium hardness as CaCO₃ (ppm)

50–500

Below 600

Below 600

Chlorides (ppm)

Below 300

Below 500

Below 2,000

Silica (ppm)

Below 150

Below 150

Below 150


Source: EVAPCO Operation and Maintenance Instructions for Coolers and Condensers, June 2025. These are illustrative manufacturer guidelines, not universal operating limits. Refer to the applicable equipment manufacturer's recommendations, including any additional conditions and limitations. 


Notice how some of these acceptable parameter's change depending on the materials of construction. Does your water treatment representative know what materials your condenser coils are manufactured from, or are they simply treating the water based on a conventional cooling tower application?


What if ammonia is introduced into the condenser water?

Another important consideration that separates ammonia refrigeration evaporative condensers from conventional cooling towers is the potential for refrigerant contamination of the recirculating water. If a condenser coil develops a leak, ammonia can dissolve into the sump water and potentially cause changes in water chemistry, including:

  • Increased pH.

  • Changes in electrical conductivity.

  • Increased ammonia concentrations.

  • Increased demand on certain oxidizing biocides.

  • Formation of chloramines when ammonia reacts with chlorine-based treatments.


These changes can complicate the effectiveness of the existing water treatment program.

Imagine an automated chemical feed system detecting an elevated pH and attempting to correct the water chemistry without anyone investigating why the pH increased in the first place.


An unexpected change in water chemistry should not always be treated as a chemical amount problem. It could be an indication of a mechanical integrity problem within the refrigeration system. Elevated pH alone does not confirm an ammonia leak, but unexplained changes should be investigated.


Who is monitoring the water between service visits?

A water treatment representative may visit your facility weekly, biweekly, or even monthly. However, your refrigeration system may be operating 24 hours a day, seven days a week. A lot can change between those service visits.


Chemical metering pumps can fail, chemical drums can become empty, conductivity probes can become contaminated, blowdown valves can malfunction, and makeup water conditions can change. Evaporative condensers often have relatively small recirculating water volumes compared to their heat rejection capacity, meaning water chemistry can change relatively quickly.


This is where refrigeration operators become an essential part of a successful water treatment program. Your water treatment program is also part of your energy management program. The accumulation of scale creates additional thermal resistance between the refrigerant and the water being circulated over the condenser coils. As this accumulation increases, the condenser's ability to reject heat decreases.


This can contribute to:

  • Increased condensing temperatures and pressures.

  • Increased compressor compression ratios.

  • Increased compressor energy consumption.

  • Increased compressor discharge temperatures.

  • Increased condenser fan runtime.

  • Reduced overall refrigeration system capacity and efficiency.


At MySafety, we frequently emphasize the importance of trending operational data rather than simply documenting numbers during daily equipment rounds. The same concept applies to condenser water chemistry. However, an operator who is trending the water chemistry may recognize that something is changing several days before the acceptable operating limit is exceeded.


This provides an opportunity to investigate the condition before it becomes a more significant problem. Automated monitoring systems are excellent tools, but collecting data and understanding data are two entirely different things.


Questions to ask your water treatment representative

The next time your water treatment representative visits your facility, consider having your refrigeration operators participate in the visit and ask some of the following questions:

  • What chemicals are we introducing into our condenser sumps, and what is their intended purpose?

  • Are these chemicals compatible with all the materials of construction within our condensers?

  • What are our established water chemistry operating limits?

  • What cycles of concentration are we targeting, and why?

  • What happens if a chemical metering pump fails?

  • What changes in water chemistry could indicate an ammonia leak?

  • Has our water chemistry been operating outside acceptable limits between service visits?

  • What conditions should our refrigeration operators monitor during their routine equipment rounds?

  • Who is responsible for responding to abnormal water conditions?


Final Thoughts:

We fully support utilizing qualified third-party companies to assist facilities with specialized services. However, we also believe that refrigeration operators should understand every aspect that influences the safety, reliability, and efficiency of their refrigeration systems. The objective is not to challenge the expertise of your water treatment provider but rather to establish better communication between two specialized trades that are both responsible for contributing to the reliability of the same piece of equipment.


Stay tuned to the MySafety blogs. Reach out to us if you have additional questions or concerns. Our team will be pleased to assist you.


Our community can't grow without you, and we deeply appreciate your support.

Please LIKE, SHARE, and FOLLOW our content on social media platforms.


Join our newsletter mailing list to stay up to date on our latest blogs/articles and information.


KEEP IT COOL & SAFE!


Ammonia refrigeration sump controller.
Ammonia refrigeration sump controller

Comments


bottom of page